| Technical specifications |
| Digital input/output |
| Digital type | 5 V TTL input/CMOS output |
| Number of I/O | One port of 8 bits, shared with temperature alarms |
| Configuration | Each bit can be independently configured for input or output. |
| Power on conditions | Power on reset is input mode, except when bits are con-figured to operate as alarms. |
| Pull-up/pull-down configuration | The port has 47 k? resistors configurable as pull-up (default) or pull-down via internal jumper W1. |
| Digital I/O transfer rate (system paced) | 100 to 5000 reads/writes per second typ on a local networkThis is the typical throughput when the device and host are both connected by Ethernet to the same local network. Throughput can vary significantly, and typical throughput is not guaranteed, if a wireless connection is involved or data is sent over the internet. |
| Power on and reset state | All bits are input unless the temperature alarm func-tionality is enabled for them. |
| Input high voltage threshold | 2.0 V min |
| Input high voltage limit | 5.5 V absolute max |
| Input low voltage threshold | 0.8 V max |
| Input low voltage limit | –0.5 V absolute min, 0 V recommended min |
| Output high voltage | 4.4 V min (IOH = –50 µA); 3.76 V min (IOH = –24 mA) |
| Output low voltage | 0.1 V max (IOL = 50 µA); 0.44 V max (IOL = 24 mA) |
| Temperature alarms |
| Number of alarms | 8 (one per digital I/O line) |
| Alarm functionality | Each alarm controls its associated digital I/O line as an alarm output. When an alarm is enabled, the I/O line that is associated with the alarm is set to output and driven to the appropriate state determined by the alarm options and input temperature. The alarm configurations are stored in non-volatile memory and loaded at power on. |
| Alarm input modes (T1 and T2 can be independently set for each alarm) | Alarm when input temperature >= T1, reset alarm when input temperature < T2 Alarm when input temperature <= T1, reset alarm when input temperature >T2 Alarm when input temperature is < T1 or > T2 |
| Alarm error modes | Alarm on temperature reading only Alarm on temperature reading or open thermocouple error Alarm on open thermocouple error only |
| Alarm output modes | Disabled, digital I/O line may be used for normal operation Enabled, active high output (DIO line goes high when alarm condition is met) Enabled, active low output (DIO line goes low when alarm condition is met) |
| Alarm latency | 1 second Alarm settings are applied when changed and at power-on. Temperatures are constantly converted on enabled channels and processed for alarm conditions regardless of the communications connectivity. |
| Counter |
| Counter type | Event counter |
| Number of channels | 1 |
| Input type | Schmitt trigger; fixed 47.5 k? pull-down resistor |
| Resolution | 32 bits |
| Schmitt trigger hysteresis | 0.6V min, 1.7V max |
| Input high voltage threshold | 1.9 V min, 3.6V max |
| Input high voltage limit | 5.5 V absolute max |
| Input low voltage threshold | 1.0 V min, 2.3V max |
| Input low voltage limit | –0.5 V absolute min, 0 V recommended min |
| Input frequency | 10 MHz max |
| High pulse width | 50 ns min |
| Low pulse width | 50 ns min |
| Memory |
| EEPROM | 4,096 bytes |
| Power |
| External power supply | 5 V ±5% required; 5 V, 1 A supply provided (PS-5V1AEPS) |
| Supply current | Quiescent current 177 mA typ This is the total quiescent current requirement for the device that includes the LEDs. This value does not include any potential loading of the digital I/O bits or +VO terminal. |
| User output voltage range (available at +VO terminal) | 4.40 V min to 5.25 V max; assumes supplied AC adapter is used |
| User output current | Available at +VO terminal: 10 mA max |
| Isolation | Measurement system to chassis ground: 500 VDC min |
| LED displays and the Factory Reset button |
| Power LED (top) | On: 4.2V < Vext < 5.6V Off: Vext < 4.2V, Vext > 5.6V (power fault) Power and Activity LEDs: blink continuously in firmware update mode |
Activity LED (bottom) | On: A valid host connection is established Blinks: A command is received. Power and Activity LEDs blink continuously in firmware update mode | | Ethernet connector LEDs | Left (green): Link/activity indicator; on when there is a valid Ethernet link, and blinks when network activity is detected. Right (yellow): Speed indicator; on for 100Mbps, off for 10Mbps or no link. |
| Factory reset button | Resets network and alarm configuration settings to factory default values. |
| Environment |
| Operating temperature range | 0 °C to 55 °C |
| Storage temperature range | –40 °C to 85 °C |
| Humidity | 0 °C to 90% non-condensing |
| Mechanical |
| Dimensions | 117.9 × 82.8 × 29.0 mm (4.64 × 3.26 × 1.14 in.) |
| Screw terminal connector |
| Connector type | Screw terminal |
| Wire gauge range | 16 AWG to 30 AWG |