| Specificactions |
Output |
| DC VOLTAGE | 12 V |
| RATED CURRENT | 10 A |
| CURRENT RANGE | 0 ~ 10 A |
| RATED POWER | 120 W |
| PEAK CURRENT | 15 A |
| PEAK POWER | Note.6 180 W (3 sec.) |
| RIPPLE & NOISE (max.) | Note.2 100mVp-p |
| VOLTAGE ADJ. RANGE | 12 ~ 14V |
| VOLTAGE TOLERANCE | Note.3 ±1.0% |
| LINE REGULATION | ±0.5% |
| LOAD REGULATION | ±1.0% |
| SETUP, RISE TIME | 1500ms, 60ms/230 VAC 3000ms, 60ms/115 VAC at full load |
| HOLD UP TIME(Typ.) | 20ms/230 VAC 20ms/115 VAC at full load |
Input |
| VOLTAGE RANGE Note.7 | 88 ~ 264 VAC 124 ~ 370 VDC |
| FREQUENCY RANGE | 47 ~ 63Hz |
| POWER FACTOR (Typ.) | 0.93/230 VAC 0.96/115 VAC at full load |
| EFFICIENCY (TyINPUT p.) | 89% |
| AC CURRENT (Typ.) | 1.4 A/115 VAC 0.7 A/230 VAC |
| INRUSH CURRENT (Typ.) | 35 A/115 VAC 70 A/230 VAC |
| LEAKAGE CURRENT | < 1 mA/240 VAC |
PROTECTION |
| OVERLOAD | Normally works within 110 ~ 150% rated output power for more than 3 seconds and then shut down o/p voltage 150% rated power, constant current limiting with auto-recovery within 3 seconds and shut down o/p voltage after 3 seconds |
| OVER VOLTAGE | 14 ~ 17V Protection type : Shut down o/p voltage, re-power on to recover |
| OVER TEMPERATURE | 95°C ±5°C (TSW : detect on heatsink of power switch) Protection type : Shut down o/p voltage, recovers automatically after temperature goes down |
FUNCTION |
| DC OK REALY CONTACT RATINGS (max.) | 60 Vdc/0.3A, 30Vdc/1A, 30Vac/0.5A resistive load |
ENVIRONMENT |
| WORKING TEMP. | -25 ~ +70°C (Refer to "Derating Curve") |
| WORKING HUMIDITY | 20 ~ 95% RH non-condensing |
| STORAGE TEMP., HUMIDITY | -40 ~ +85°C , 10 ~ 95% RH |
| TEMP. COEFFICIENT | ±0.03%/°C (0 ~ 50°C) |
| VIBRATION | Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6 |
SAFETY & EMC (Note 4) |
| SAFETY STANDARDS | UL508, TUV EN60950-1 approved |
| WITHSTAND VOLTAGE | I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC O/P-DC OK:0.5KVAC |
| ISOLATION RESISTANCE | I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC / 25°C / 70% RH |
| EMC EMISSION | Compliance to EN55022 (CISPR22) Class B, EN61000-3-2,-3 |
| EMC IMMUNITY | Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN61000-6-2 (EN50082-2), EN61204-3, heavy industry level, criteria A, SEMI F47, GL approved |
OTHERS |
| MTBF | 289.9Khrs min. MIL-HDBK-217F (25 °C) |
| DIMENSION | 40*125.2*113.5mm (W*H*D) |
| PACKING | 0.67Kg; 20pcs/14.4Kg/1.16CUFT |
NOTE |
- All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25°C of ambient temperature.
- Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
- Tolerance : includes set up tolerance, line regulation and load regulation.
- The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives.
- Installation clearances : 40mm on top, 20mm on the bottom, 5mm on the left and right side are recommended when loaded permanently with full power. In case the adjacent device is a heat source, 15mm clearance is recommended.
- 3 seconds max., please refer to peak loading curves.
- Derating may be needed under low input voltage. Please check the derating curve for more details.
|