| System Specifications |
| Communication |
| Interface | RS-485 |
| Bias Resistor | Yes |
| Format | (N, 8, 1) (N, 8, 2) (E, 8, 1) (O, 8, 1) |
| Baud Rate | 1200 to 115200 bps |
| Protocol | Modbus RTU, DCON |
| Dual Watchdog | Yes, Module (1.6 Seconds), Communication (Programmable) |
| LED Indicators/Display |
> | System LED Indicator | Yes, 1 LED as Power/Communication Indicator |
| I/O LED Indicators | 8 LEDs as Analog Output and Fault Indicators |
| 7-Segment LED Display | - |
| Isolation |
> | Intra-module Isolation, Field-to-Logic | 3000 VDC |
| EMS Protection |
> | ESD (IEC 61000-4-2) | Y±8 kV Contact for each Terminal |
| RS Immunity (IEC 61000-4-3) | 3 V/m, 80 MHz ~ 1 GHz |
| EFT (IEC 61000-4-4) | ±4 kV for Power Line |
| Power |
> | Reverse Polarity Protection | Yes |
| Input Range | +10 ~ +30 VDC |
| Consumption | 4.3 W 4.8 W |
| Mechanical |
> | Dimensions (L x W x H) | 123 mm x 72 mm x 35 mm |
| Installation | DIN-Rail or Wall Mounting |
| Environment |
> | Operating Temperature | -25 to +75°C |
| Storage Temperature | -40 to +85°C |
| Humidity | 10 to 95% RH, Non-condensing |