| Technical data |
| CPU Module |
| Watchdog Timer | Yes, Module (1.6 Seconds), Communication (Programmable) |
| Isolation |
| Intra-module Isolation | 5000 Vrms |
| EMS Protection |
| EFT (IEC 61000-4-4) | ±4 kV for Power Line |
| ESD (IEC 61000-4-2) | ±4 kV Contact for each Terminal ±8 kV Air for Random Point |
| LED Indicators |
| Status | 1 x Power and Communication |
| Digital Input/Counter |
| Channels | 8 |
| Type | Wet Contact |
| Sink/Source (NPN/PNP) | Sink/Source |
| Wet Contact, ON Voltage Level | +4 ~ 30 VDC |
| Wet Contact, OFF Voltage Level | +1 VDC Max. |
| Max. Counts | 65535 (16-bit) |
| Frequency | 100 Hz |
| Min. Pulse Width | 5 ms |
| Input Impedance | 3 KO |
| Overvoltage Protection | ±35 VDC |
| Channel-to-Channel Isolation | Yes, ±2 kV for differential only |
| COM Ports |
| Ports | 1 x RS-485 |
| Baud Rate | 1200 ~ 115200 bps |
| Data Format | (N, 8, 1) (N, 8, 2) (E, 8, 1) (O, 8, 1) |
| Protocol | DCON |
| Power |
| Reverse Polarity Protection | Yes |
| Input Range | +10 ~ +30 VDC |
| Consumption | 0.2 W |
| Mechanical |
| Dimensions (mm) | 123 x 72 x 35 (W x L x H) |
| Installation | DIN-Rail |
| Environmental |
| Operating Temperature | -25 ~ +75 °C |
| Storage Temperature | -40 ~ +85 °C |
| Humidity | 10 ~ 95% RH, Non-condensing |