| Specification
|
|
MODBUS RTU CLIENT FEATURES
|
| Operation Mode |
Modbus RTU Client
|
| Function Codes Supported |
1,2,3,4,5,6, 15 & 16 |
| Swapping |
Byte and Word Swapping
|
| Maximum Modbus RTU Server Devices |
32 |
| Number Read/Write Scan Lines per RTU Server
Device |
200 Total - 100 reads & 100 writes |
| Scan Line Support |
Up to 125 Registers or 512 Coils |
|
BACNET IP SERVER FEATURES
|
| Operation Mode |
BACnet/IP Server |
| Supported Object Types |
Device, Binary I/O, Analog I/O, Character String Value |
| Supported Service Codes |
Read & Read Multiple-B, Write & Write Multiple-B, COV & COV unsolicited-B, Device Dynamic
Binding-B, Dynamic Object Binding-B |
| Maximum COV Subscriptions |
2800 |
| Analog Objects Supported |
1200 Input and 1200 Output |
| Binary Objects Supported |
1600 Input and 1600 Output |
|
INCLUDED WITH GATEWAY
|
| 3’ power cable with flying leads |
5-year hardware warranty |
| IPSetup software – automatically locates RTA
gateway on the network |
Unlimited firmware feature upgrades for life |
| CAT5 crossover cable for direct connection to PC
during programming |
Complete, unlimited access to our industry leading support staff |
| Manual |
|
|
ELECTRICAL / ENVIRONMENTAL
|
| DC Input Voltage |
8 VDC @ 230mA to 28 VDC @ 80 mA |
| Maximum Baud Rate |
115K baud |
| Operating Temperature |
-40 C to 85 C |
| Certification |
RoHS-Compliant, UL, CUL, CE Approvals, Class
I Div 2 |
|
ENCLOSURE / HARDWARE
|
| Size |
4.2" x 3.25" x 1" |
| Weight |
7 oz |
| Enclosure Type |
Anodized Aluminum |
| Mounting |
Din rail or panel mount |
| LEDs |
Ethernet link/data LED, Ethernet speed LED,
power LED, & 2 general purpose LEDs on side |
|
GATEWAY FEATURES & FUNCTIONS
|
| Alarming |
Set <, <=, >, >=, ==, !=, and change-of-state rules on
any data moving through the gateway. If alarm rule
is triggered an email notification can be sent. |
| Gateway Security |
You can configure up to 9 different users access to diagnostic and configuration screens. |
| Translation Table |
Allows for data manipulation during protocol
translation. Scaling and other data format changes
can occur in the gateway. |
| Status and Counters |
Protocol specific status, counters, ande error messages are accessible within the gateway’s
diagnostics page. They can also be delivered to a
connected device. |
| Diagnostic Logging Page |
Allows users to see and log start up sequences,
protocol specific messages & error messages. |