| Technical Specifications |
| Modbus RTU Master FEATURES |
| Operation Mode | Modbus RTU Master |
| Function Codes Supported | 1,2,3,4,5,6,15 & 16 |
| Swapping | Byte and Word Swapping |
| Maximum Modbus RTU Slave Devices | 32 |
| Number Read/Write Scan Lines per RTU Slave Device | 200 Total - 100 reads & 100 writes |
| Scan Line Support | Up to 125 Registers or 512 Coils |
| ASCII FEATURES |
| Operation Mode | Bidirectional ASCII Transmit and Receive |
| Maximum Number of Devices Supported | 2 |
| Concatenation | Concatenate up to 50 segments data in a delimeted ASCII sting |
| Maximum Number of ASCII Characters Transferred | 1024 in each direction |
| Delimiter Processing | Incoming delimiters can be automatically removed; Outgoing delimiters automatically added if configured |
| Parsing | Parse string of ASCII data in up to 50 segments by delimiter or offset |
| ELECTRICAL / ENVIRONMENTAL DIMENSIONS |
| DC Input Voltage | 8 VDC @ 230mA to 28 VDC @ 80 mA |
| Maximum Baud Rate | 115K baud |
| Operating Temperature | -40 C to 85 C |
| Certification | RoHS-Compliant, UL, CUL, CE Approvals, Class I Div 2 |
| ENCLOSURE / HARDWARE |
| Size | 4.2? x 3.25? x 1? |
| Weight | 7 oz |
| Enclosure Type | Anodized Aluminum |
| Mounting | Din rail or panel mount |
| LEDs | Ethernet link/data LED, Ethernet speed LED, power LED, & 2 general purpose LEDs on side |
| GATEWAY FEATURES & FUNCTIONS |
| Alarming | Set <, <=, >, >=, ==, !=, and change-of-state rules on any data moving through the gateway. If alarm rule is triggered an email notification can be sent. Gateway Security You can configure up to 9 different users access to diagnostic and configuration screens. |
| Translation Table | Allows for data manipulation during protocol translation. Scaling and other data format changes can occur in the gateway. |
| Status and Counters | Protocol specific status, counters, and error messages are accessible within the gateways diagnostics page. They can also be delivered to a connected device. |
| Diagnostic Logging | Page Allows users to see and log start up sequences, protocol specific messages & error messages. |