| TECHNICAL SPECIFICATIONS |
| General Data |
| Power supply | 10..40 Vdc / 19..28 Vac |
| Power Consumption | 1 W |
| Isolation | 1.5 kVac (6 way) |
| Input protection | Against ESD discharge up to 4KV |
| Status Indicator | Power - Communication Fault input |
| Response Time | < 28ms |
| Accuracy | 0,05% |
| A/D Resolution | 13 or 14 bit |
| Thermal Drift | <50 ppm/°C |
| Dimension | 17,5 x 110 x 112 mm |
| Housing | Nylon 6 with 30% glass-fiber, V0 self-extinguished class |
| Weight | About 170 g |
| Operating Temperature | -10..+65°C |
| Connections | Removable screw terminals, IDC10 connector for Z-PC-DIN backplane 3.5 mm RS232, front jack |
| Protection Degree | IP20 |
| Configuration | DIP switches (baud rate, Node ID) - EDS file - IEC 61131 |
| Protocols supported | EDS file IEC 61131 CAN bus standard (2.0A, 2.0B) CANopen (profile CiA 401 v.2.01) |
| CANopen max speed | 1Mbps |
| Norms & Approvals | CE, EN 61000-6-4, EN 64000- 6-2, EN 61010-1 CAN 2.0A, 2.0B CiA 401 v.2.01 IEC EN 61131-2 |
| OUTPUT DATA |
| Channels | 3 |
| Type | Voltage : ±10V Current : 0-20, 4..20 mA |
| INPUT DATA |
| Channels | 4, RTD with 2,3,4 wires, fully isolation |
| Type | PT100 (EN 60751/A2-ITS90), -200..+650°C PT500 (EN 60751/A2-ITS90), -200..+750°C PT1000 (EN 60751/A2-ITS90), -200..+210°C Ni100 (EN 60751/A2-ITS90), -60..+250°C |
| CANOPEN FEATURES |
| NMT | Slave |
| Error Control | Node Guarding |
| Node ID | Free software - DIP switches |
| Nr.PDO | RX 5 |
| PDO modes | Event triggered Synq (cyclic) - Synq (acyclic) |
| PDO linking | yes |
| PDO mapping | variable |
| Nr. SDO server | 1 |
| Emergency message | yes |
| Application layer | CiA 301 v4.02 |
| Profile | CiA 401 v2.01 |