| TECHNICAL SPECIFICATIONS |
| Electrical Specifications |
| Power supply | 10..40 Vdc / 19..28 Vac / 50-60 Hz |
| Power consumption | 1,5 W |
| Isolation | 1.500 Vac (3 way) |
| Power transducers | Yes |
| Status Indicators | Power Fail Rx / Tx Active output |
| Protection Degree | IP20 |
| Thermomechanical Specifications |
| Operating Temperature | -10..+65 °C |
| Dimension (W x H x ) | 17.5 x 100 x 112 mm |
| Weight | About 140 g |
| Enclosure | Nylon 6 with 30% glass-fiber, V0 self-extinguished class |
| Connections | -Removable terminals block, plug in connectors, max wire size 2,5 mm2 -Rear IDC10 connector for Z-PC backplane |
| Mounting | 35 mm DIN rail guide |
| Communication, Memory process |
| Interface | 2 wire RS485 |
| Speed | Up to 57.600 bps |
| Protocol | ModBUS RTU slave |
| Communication Time | < 10 ms (38400 baud) |
| Distance | Up to 1.200 m |
| Connectivity | Max 32 nodes |
| Data Memory | EEPROM for the configuration parameters, retention time 10 years, N° 5 registers 16 bit, N° 5 bit overflow |
| Signals |
| Channel Numbers | 5 |
| Type | SPST N.O. relay output with common line Max rated current: 5 A Max switching voltage: 250 Vac Relay working voltage: 24 Vdc Relay absorbed current: 9 mA Release time delay: 5 / 2 ms |
| Configuration |
| DIP switches | Baud rate, node, parity, serial port, bit stop, termination line |
| Software | Z-NET3 (Iec 61131) EASY Z-D-IN (plug&play |
| Configuration |
| Approval | CE, RINA |
| Norms | EN 50081-2; EN 55011; EN 50082-2; EN 61000-2-2/4; EN 50140/141; EN 61010-1 |