Specifications |
Analog Input |
Input Channels |
8 (Differential) |
Input Type(jumper selectable) |
+/-15 mV, +/-50 mV, +/-100 mV, +/-150 mV, +/-500 mV, +/-1 V, +/-5 V, +/-10 V |
Thermocouple (J, K, T, E, R, S, B, N, C, L, M,LDIN43710) |
+/-20mA, 0~20mA, 4~20mA |
Resolution |
16-bit |
Sampling Rate |
10 Samples/Sec. (Total) |
Accuracy |
+/-0.1% |
Zero Drift |
+/-0.5 µV/°C |
Span Drift |
+/-25 µV/°C |
Input Impedance |
Voltage |
1 MO |
Current |
125 O |
Common Mode Rejection |
86 dB Min. |
Normal Mode Rejection |
100 dB |
Over Voltage Protection |
240 Vrms |
Individual Channel Configuration |
Yes |
Open Wire Detection |
Yes |
Digital Output |
Output Channels |
4 |
Output Type |
Isolated Open Collector (Sink) |
Max. Load Current |
700 mA/Channel |
Load Voltage |
5 VDC ~ 50 VDC |
Overvoltage Protection |
60 VDC |
Overload Protection |
1.4 A |
Short-circuit Protection |
Yes |
System |
CPU |
16-bit CPU
|
SRAM |
512 KB |
Flash Memory |
512 KB |
EEPROM |
16 KB |
Watchdog |
Yes |
Communication |
PoE Ethernet Port |
10/100 Base-TX (With Link, Activity LED Indicator) and automatic MDI/MDI-X |
2-way Isolation
|
I/O |
2500 VDC
|
LED Indicators
|
PoE |
PoE On |
L1 |
System Running |
L2 |
Ethernet Link/Act |
L3 |
Ethernet 10/100M Speed |
Power Requirements
|
Reserve Polarity Protection |
Yes |
Powered from terminal block |
Yes, 12 ~ 48 VDC |
Powered from PoE |
Yes, IEEE 802.3af, Class1 |
Consumption |
3.4 W |
Mechanical
|
Dimensions (W x H x D) |
123 mm x 72 mm x 35 mm |
Installation |
DIN-Rail or Wall mounting |
Environment
|
Operating Temperature |
-25°C ~ +75 °C |
Storage Temperature |
-30°C ~ +80 °C |
Relative Humidity |
5 ~ 90% RH, non-condensing |
Software Specifications |
Functions |
Rule Configuration Website |
Access Web server on WISE controllers to edit and upload logic rules through web browser. |
36 IF-THEN-ELSE Logic Rules |
3 IF conditions with AND or OR operators |
3 THEN actions and 3 ELSE actions |
48 Internal Registers |
Hold temporary variables and read/write data via Modbus/TCP address. |
12 Timers |
Delay / Timing functions. |
12 Emails |
Send Email messages to pre-set Email receivers. |
12 CGI Commands |
Send pre-set CGI commands. |
12 Recipes |
Set up THEN/ELSE action groups. |
8 P2P remote modules |
Set up the connection information for the remote WISE modules. |
Modbus/ TCP Protocol |
Real time control and monitoring I/O channels and system status of controllers via SCADA software. |
IF Conditions |
AI Channel |
=, >, <, >=, <=(value) |
Internal Register
|
DO Counter |
=, >, <, >=, <=(value), Change |
Timer |
Timeout, Not Timeout. |
P2P |
DI, AI, DI counter, DO counter, IR |
Rule Status |
Enable, Disable. |
THEN / ELSE Actions |
DO Channel |
ON, OFF, Pulse Output |
Internal Register |
Change the value |
DO Counter |
Reset |
Timer |
Start, Stop |
Email |
Send |
CGI Commands
|
Recipe |
Execute |
P2P |
DO(On/Off), AO, IR |
Rule Status |
Enable, Disable. |