Specifications |
Analog Input |
Input Channels |
10 (Differential) |
Input Type |
+/-15 mV, +/-50 mV, +/-100 mV, +/-500 mV,+/-1 V, +/-2.5 V |
+/-20 mA, 0 ~ 20 mA, 4 ~ 20 mA (Requires Optional External 125 O Resistor) |
Thermocouple (J, K, T, E, R, S, B, N,C, L, M, LDIN43710) |
Resolution |
16-bit |
Sampling Rate |
10 Samples/Sec. (Total) |
Accuracy |
+/-0.1% |
Bandwidth |
15.7 Hz |
Zero Drift |
+/-0.5 µV/°C |
Span Drift |
+/-25 µV/°C |
Input Impedence |
>300 kO |
Common Mode Rejection |
150 dB Min |
Normal Mode Rejection |
100 dB |
Overvoltage Protection |
240 Vrms |
Open Thermocouple Detection |
Yes |
Individual Channel Configuration |
Yes |
ESD Protection |
+/-4 kV (Contact for each channel) |
+/-8 kV air for random point |
EFT Protection |
+/-4 kV for Power |
Digital Output |
Output Channels |
6 (Sink) |
Output Type |
Isolated Open Collector |
Max. Load Current |
700 mA/Channel |
Load Voltage |
5 VDC ~ 50 VDC |
System |
CPU |
80186 CPU (80 MHz) |
SRAM |
512 KB KB |
Flash Memory |
512 KB |
EEPROM |
16 KB |
Dual Watchdog |
Yes |
Communication |
PoE Ethernet Port |
10/100 Base-TX (With Link, Activity LED Indicator) and automatic MDI/MDI-X |
2 Way Isolaiton |
Ethernet |
1500 Vrms |
AI and DO |
2500 Vrms |
LED Indicators |
PoE |
PoE On |
L1 |
Run |
L2 |
Link/Act |
L3 |
10/100M |
Power Requirements |
IEEE 802.3af |
Class 1 |
Required Supply Voltage |
Powered by Power over Ethernet (PoE) or auxiliary power +12 VDC ~ +48 VDC (non-regulated) |
LED Indicator |
Yes |
Power Consumption |
0.12 A @ 24 VDC Max. |
Mechanical |
Dimensions (W x H x D) |
72 mm x 123 mm x 35 mm |
Installation |
DIN-Rail or Wall Mounting |
Environment |
Operating Temperature |
-25°C ~ +75°C |
Storage Temperature |
-30°C ~ +80°C |
Ambient Relative Humidity |
5 to 90% RH, non-condensing |
Software Specifications |
Functions |
36 IF-THEN-ELSE Logic Rules |
3 IF conditions with AND or OR operators |
3 THEN actions |
3 ELSE actions |
48 Internal Registers |
Hold temporary variables and read/write data via Modbus/TCP address. |
12 Timers |
Delay / Timing functions. |
12 Emails |
Send Email messages to pre-set Email receivers. |
Rule Configuration Website |
Access Web server on WISE controllers to edit and upload logic rules through web browser. |
Modbus/ TCP Protocol |
Real time control and monitoring I/O channels and system status of controllers via SCADA software. |
IF Conditions |
AI Channel |
=, >, <, >=, <=(value) |
Internal Register
|
DO Counter |
=, >, <, >=, <=(value), Change |
Timer |
Timeout, Not Timeout. |
THEN / ELSE Actions |
DO Channel |
ON, OFF, Pulse Output |
Internal Register |
Change the value |
DO Counter |
Reset |
Timer |
Start, Stop |
Email |
Send |