Specifications |
Analog Input |
Input Channels | 7 (Differential) |
Sensor Type | Pt100, Pt1000, Ni120, Cu100, Cu1000 |
Wire Connection | 2/3 wire |
Resolution | 16-bit |
Sampling Rate | 12 Samples/Sec. (Total) |
Accuracy | +/-0.05% |
Zero Drift | +/-0.5 µV/°C |
Span Drift | +/-20 µV/°C |
Common Mode Rejection | 150 dB |
Normal Mode Rejection | 100 dB |
Input Impedence | > 1M O |
Open Wire Detection | Yes |
Individual Channel Configuration | Yes |
3-wire RTD Lead Resistance Elimination | Yes |
System |
CPU | 16-bit CPU |
SRAM | 512 KB KB |
Flash Memory | 512 KB |
EEPROM | 16 KB |
Watchdog | Yes |
Communication |
PoE Ethernet Port | 10/100 Base-TX and automatic MDI/MDI-X |
2 Way Isolaiton |
I/O | 2500 Vrms |
EMS Protection |
ESD (IEC 61000-4-2) | ±4 kV Contact for each terminal and ±8 kV Air for random point |
EFT (IEC 6000-4-4) | ±4 kV for Power Line |
LED Indicators |
PoE | PoE On |
L1 | System Running |
L2 | Ethernet Link/Act |
L3 | Ethernet 10/100M Speed |
Power Requirements |
Reserve Polarity Protection | Yes |
Powered from terminal block | Yes, 12 ~ 48 VDC |
Powered from PoE | Yes, IEEE 802.3af, Class 1 |
Consumption | 2.6 W |
Mechanical |
Dimensions (W x H x D) | 72 mm x 123 mm x 35 mm |
Installation | DIN-Rail or Wall Mounting |
Environment | Operating Temperature | -25°C ~ +75°C (-13°F ~ +167°F) |
Storage Temperature | -30°C ~ +80°C (-22°F ~ +176°F) |
Ambient Relative Humidity | 5 to 90% RH, non-condensing |
Software Specifications |
Functions |
Rule Configuration Website | Access Web server on WISE controllers to edit and upload logic rules through web browser. |
36 IF-THEN-ELSE Logic Rules | 3 IF conditions with AND or OR operators |
3 THEN actions and 3 ELSE actions |
48 Internal Registers | Hold temporary variables and read/write data via Modbus/TCP address. |
12 Timers | Delay / Timing functions. |
12 Emails | Send Email messages to pre-set Email receivers. |
12 CGI Commands | Send pre-set CGI commands. |
12 Recipes | Set up THEN/ELSE action groups. |
8 P2P Remote | Set up the connection information for the remote WISE modules. |
Modbus/ TCP Protocol | Real time control and monitoring I/O channels and system status of controllers via SCADA software. |
IF Conditions |
AI Channel | =, >, <, >=, <=(value) |
Internal Register |
Timer | Timeout, Not Timeout. |
P2P | DI, AI, DI counter, IR |
Rule Status | Enable, Disable |
THEN / ELSE Actions |
Internal Register | Change the value |
Timer | Start, Stop |
Email | Send |
CGI Commands |
Recipe | Execute |
P2P | DO (On/Off), AO, IR |
Rule Status | Enable, Disable |