Specifications |
Analog Input |
Input Channels |
7 (Differential) |
Sensor Type |
Pt100, Pt1000, Ni120, Cu100, Cu1000 |
Wire Connection |
2/3 wire |
Resolution |
16-bit |
Sampling Rate |
12 Samples/Sec. (Total) |
Accuracy |
+/-0.05% |
Zero Drift |
+/-0.5 µV/°C |
Span Drift |
+/-20 µV/°C |
Common Mode Rejection |
150 dB |
Normal Mode Rejection |
100 dB |
Input Impedence |
> 1M O |
Open Wire Detection |
Yes |
Individual Channel Configuration |
Yes |
3-wire RTD Lead Resistance Elimination |
Yes |
System |
CPU |
16-bit CPU |
SRAM |
512 KB KB |
Flash Memory |
512 KB |
EEPROM |
16 KB |
Watchdog |
Yes |
Communication |
PoE Ethernet Port |
10/100 Base-TX and automatic MDI/MDI-X |
2 Way Isolaiton |
I/O |
2500 Vrms |
EMS Protection |
ESD (IEC 61000-4-2) |
±4 kV Contact for each terminal and ±8 kV Air for random point |
EFT (IEC 6000-4-4) |
±4 kV for Power Line |
LED Indicators |
PoE |
PoE On |
L1 |
System Running |
L2 |
Ethernet Link/Act |
L3 |
Ethernet 10/100M Speed |
Power Requirements |
Reserve Polarity Protection |
Yes |
Powered from terminal block |
Yes, 12 ~ 48 VDC |
Powered from PoE |
Yes, IEEE 802.3af, Class 1 |
Consumption |
2.6 W |
Mechanical |
Dimensions (W x H x D) |
72 mm x 123 mm x 35 mm |
Installation |
DIN-Rail or Wall Mounting |
Environment |
Operating Temperature |
-25°C ~ +75°C (-13°F ~ +167°F) |
Storage Temperature |
-30°C ~ +80°C (-22°F ~ +176°F) |
Ambient Relative Humidity |
5 to 90% RH, non-condensing |
Software Specifications |
Functions |
Rule Configuration Website |
Access Web server on WISE controllers to edit and upload logic rules through web browser. |
36 IF-THEN-ELSE Logic Rules |
3 IF conditions with AND or OR operators |
3 THEN actions and 3 ELSE actions |
48 Internal Registers |
Hold temporary variables and read/write data via Modbus/TCP address. |
12 Timers |
Delay / Timing functions. |
12 Emails |
Send Email messages to pre-set Email receivers. |
12 CGI Commands |
Send pre-set CGI commands. |
12 Recipes |
Set up THEN/ELSE action groups. |
8 P2P Remote |
Set up the connection information for the remote WISE modules. |
Modbus/ TCP Protocol |
Real time control and monitoring I/O channels and system status of controllers via SCADA software. |
IF Conditions |
AI Channel |
=, >, <, >=, <=(value) |
Internal Register
|
Timer |
Timeout, Not Timeout. |
P2P |
DI, AI, DI counter, IR |
Rule Status |
Enable, Disable |
THEN / ELSE Actions |
Internal Register |
Change the value |
Timer |
Start, Stop |
Email |
Send |
CGI Commands |
Recipe |
Execute |
P2P |
DO (On/Off), AO, IR |
Rule Status |
Enable, Disable |