GENERAL DATA |
Power Supply |
Loop powered (6..100 V) |
Power Consumtption |
<< 21 mA |
Isolation / Protection |
3 kVdc (on bare conductors) |
LED Status Indicators |
- |
Overvoltage category |
300 V CAT III (bare conductor) 600 V CAT III (isolated conductor) |
Measurement polarity |
Positive (incoming current on label side) |
Protection degree |
IP20 |
Accuracy class |
AC: 0,2% f.s. |
Settings |
DIP switch |
Log Data |
- |
Operating temperature |
10..+65°C |
Storage temperature |
40..+85°C |
Humidity |
10rH..90% non condensing |
Altitude |
Up to 2.000 m.a.s.l. |
Connections |
Removable terminals (5 poles), pitch 5 mm for cable up to 2,5 mm2 |
Max diameter conductor |
12,3 mm |
Dimension (wxhxd) |
41x44x26 mm |
Mounting |
Free or on DIN rail IEC EN 60715 (35 mm) with accessories |
Case |
PA6, black |
Weight |
47 g |
INPUT DATA |
Channels |
1 |
Range |
"Monopolar: 0..5, 0..10, 0..20,0.. 40 A Bipolar: -5..5, -10..10, -5..20, -10..40 A” |
Measurement type |
Magnetic balance |
Bipolar measurement |
yes |
Hysteresis |
- |
Max instantaneous overcurrent |
800 A |
Bandwidth/frequency |
n.d. |
Crest factor |
1,2 |
OUTPUT DATA |
Channels |
1 |
Range |
4..20 mA (2 fili) |
Resolution |
12 bit |
Max load |
- |
EMI Error |
< 50µA |
Thermal drift |
< 150 ppm/K |
Response time |
100 ms (without filter) 600 ms (with filte |
STANDARD |
Approvals |
CE, UL-UR, european patent |
Norms |
EN61000-6-4 EN61000-6-2 EN61010-1 |