| Technical data |
| GENERAL DATA |
| Power supply | 11,5..28 Vdc |
| Power consumption | 21 mA excluding load |
| Isolation and protection | 3 kVdc (on bare conductors) |
| LED status indicators | Power supply/USB communication/Digital output |
| Overvoltage category | 300 V CAT III (bare conductor) 600 V CAT III (isolated conductor) |
| Measurement polarity | Positive (incoming current on label side) |
| Data configuration and export | DIP Switch, Software (EASY SETUP) |
| Protection degree | IP20 |
| Accuracy class | 0,5% f.s. (DC bipolar, AC TRMS) |
| Operating temperature | -25..+70°C |
| Storage Temperature | -40..+85°C |
| Humidity | 10% – 90% non condensing |
| Altitude | Up to 2.000 m.a.s.l. |
| Connections | Removable terminals (5 poles), pitch 5 mm for cable up to 2,5 mm2 Micro USB (programming) |
| Through hole diameter | 35 mm |
| Dimension (wxhxd) | 95 x 75 x 35 mm |
| Mounting | Free or on DIN rail IEC EN 60715 (35 mm) with accessories |
| Case | PA6, black color |
| Weight | 150 g |
| COMMUNICATION |
| Communication Port | RS485/Micro USB |
| Protocol | ModBUS RTU slave |
| Data rate | 1.200..115.200 bps |
| INPUT DATA |
| Channels | 1 |
| Range | 0-300/-600 Aac/dc TRMS; ±300/±600 Adc Bipolar |
| Measurement type | AC/DC TRMS o DC Bipolar |
| Bipolar measurement | Yes |
| Overload | 3xIIN direct; 2.000 A (impulsive) |
| Bandwidth | 1 kHz |
| Crest factor | 2 |
| OUTPUT DATA |
| Analog channels | 1 |
| Range | 0..10 V |
| Resolution | 13 bits (10.000 points) |
| Min Load | 2 kOhm |
| EMI error | <0,5% |
| Thermal drift | < 200 ppm/K |
| Hysteresis measurement | 0,2% f.s. |
| Response time | Fast filter: 800 ms Slow filter: 2 s |
| Digital channels | 2 |
| Function | Alarm (alternative to analog channel) |
| Type | PNP active output, max. load 50 mA |
| STANDARD |
| Approvals | CE |
| Norms | EN61000-6-4 EN61000-6-2 EN61010-1 |