ANALOG INPUT MODULAR INDICATORS / TOTALIZERS |
GENERAL DATA |
Power supply | 80-265 Vac (H version) 10-40 Vdc / 19-28 Vac (L version) |
Power transducers | Max 18 V, 25 mA |
Power consumption | Max 3 W |
Isolation | 1.500 Vac |
Communication interface | ModBUS RTU slave (optional board) |
Memory | EEPROM 10 years storage memory |
VISUALIZATION AND MEASURE |
Display | LED, 8 digit |
Status indicators | 2 alarm leds (enabled threshold trips) |
Front Buttons | 3 navigation keys |
Display errors | Over range, fault sensor |
INPUT DATA |
CH | 1 |
Type | Contact, Reed, Npn 2 / 3 wire, Pnp 3 wire with 24 Vdc power supply, Namur, photoelectric, variable reluctance, 24V pulse, TTL |
Frequency | 0.001 – 9.9999 Hz |
Reset (totalizer) | Yes: by digital input and front keys |
OUTPUT DATA |
CH | 1 |
Type | 0-10 V (min 1K) 0-20 / 4-20 mA (max 500 ohm) |
Resolution | 10.000 points |
Optional board | Nr 2 SPDT 220 Vac (5A resistive, 2 A inductive) relay alarms + Nr 1 RS485ModBUS RTU slave port + nr 1 reset digital input |
THEMOMECHANICS DATA |
Operating temperature | 10..+60 °C |
Case | PPO self-extinguish DIN 43700 |
Protection degree | IP65 (frontal) |
Terminal blocks | Removable, step 3,5 – 5,08 mm |
Dimension (W x H x D) | 96x48x98 mm |
Panel dimension | 91x45 mm |
Weight | 200 g |
SETTINGS, NORMS |
Software / settings | Display parameters, alarms, signals, timeout, reset, trips |
Calibration | Yes, factory-made |
Norms | EN 61000-6-4/2002, EN 61000-6-2/2005, EN 61010-1/2001 |