| ANALOG INPUT MODULAR INDICATORS / TOTALIZERS |
| GENERAL DATA |
| Power supply | 80-265 Vac (H version) 10-40 Vdc / 19-28 Vac (L version) |
| Power transducers | Max 18 V, 25 mA |
| Power consumption | Max 3 W |
| Isolation | 1.500 Vac |
| Communication interface | ModBUS RTU slave (optional board) |
| Memory | EEPROM 10 years, storage memory |
| VISUALIZATION AND MEASURE |
| Display | LED, 4 digit |
| Status indicators | 2 alarm leds (enabled threshold trips) |
| Front Buttons | 3 navigation keys |
| Display errors | Over range, fault sensor |
| Accuracy | 0,10% |
| Stability | 0,01%/K |
| Linearity error | 0,2°C (Pt100) 0,5° (TC J,K,E,N,T) 1°C (TC R,S) 2°C (TC B) 0,05% (0-10 V, 0-20 mA) |
| Cold joint | ±1,5°C |
| INPUT DATA |
| CH | 1 |
| Type | Voltage: 0-10 V Active / passive current: 0-20 / 4..20 mA Potentiometer: 1..100 k1 Pt100 2,3,4 wire (IEC 751 / EN 60751 – ITS90) Thermocouple J,K,R,S,T,B,E,N |
| Resolution | 14 bit |
| Sampling time | 20 ms |
| Reset (totalizer) | Yes: by digital input and front keys |
| THEMOMECHANICS DATA |
| Operating temperature | -10..+60 °C |
| Enclosure | PPO self-extinguish DIN 43700 |
| Protection degree | IP65 (frontal) |
| Terminal blocks | Removable, step 3,5 – 5,08 mm |
| Dimension (W x H x D) | 96x48x98 mm |
| Panel cut -out | 91x45 mm |
| Weight | 200 g |
| SETTINGS, NORMS |
| Software / settings | Display parameters, alarms, signals, timeout, reset, trips |
| Calibration | Yes, factory-made |
| Norms | EN 61000-6-4/2002, EN 61000-6-2/2005, EN 61010-1/2001 |