System Specifications |
Communication |
Interface |
RS-485 |
Format |
N, 8, 1), (N, 8, 2), (E, 8, 1), or (E, 8, 2) |
Baud Rate |
1200 ~ 115200 bps |
Protocol |
Modbus RTU, DCON |
Dual Watchdog |
Yes, Module (1.6 Seconds), Communication (Programmable) |
LED Indicators/Display |
System LED Indicator |
Yes, 1 LED as Power/Communication Indicator |
Isolation |
Intra-module Isolation, Field-to-Logic |
3000 VDC |
EMS Protection |
ESD (IEC 61000-4-2) |
±4 kV Contact for each Terminal |
EFT (IEC) 610004-4) |
±4kV for Power Line |
Surge (IEC 610004-5) |
±0.5 kV for Power Line |
Power |
Reverse Polarity Protection |
Yes |
Input Range |
10~30VDC |
Consumption |
1.3 W |
Mechanical |
Dimensions (W x L x H) |
72 mm x 123 mm x 35 mm |
Installation |
DIN-Rail or Wall Mountable |
Environment |
Operating Temperature |
-25°C to +75°C (-13°C ~ +167°F) |
Storage Temperature |
-40°C to 85°C (-40°F ~ +185°F) |
Humidity |
10 to 95%, Non-condensing |