Specifications |
Communication
|
Interface |
RS-485 |
Format |
(N, 8, 1), (N, 8, 2), (O, 8, 1), (E, 8, 1) |
Baud Rate |
1200 ~ 115200 bps |
Protocol |
DCON |
Watchdog |
Dual Watchdog |
Yes, Module (1.6 seconds), Communication (Programmable) |
LED Indicators
|
1 LED as Power Indicator |
8 LEDs as PhotoMOS Output Indicators |
Isolation |
Intra-module Isolation, Field-to-Logic |
5000 VDC |
Isolation |
ESD (IEC 61000-4-2) |
±4 kV Contact for Each Terminal |
±8 kV Air for Random Point |
EFT (IEC 61000-4-4) |
±4 kV for Power |
Power |
Power Consumption |
0.3 W (Max.) |
Environment |
Operating Temperature |
-25°C ~ +75°C |
Storage Temperature |
-30°C ~ +80°C |
Humidity |
10 ~ 90 % RH, non-condensing |
Dimensions |
30 mm x 102 mm x 115 mm (W x L x H) |
I/O Expansion |
PhotoMOS Relay Output
|
Output Channels |
8 |
Relay Type |
PhotoMOS Relay, Form A |
Operating Load Voltage Range |
350 V (AC peck or DC) |
Countinous Load Current |
0.13 A |
Peak Load Current |
0.4 A |
Output Off State Leakage Current |
1 µA |
Operating Time |
2 ms (Max.) |
Release Time |
1 ms (Max.) |
Electrical Endurance |
No Arcing, No Bounce, and No Switching Noise |
Power-on Value |
Yes, Programmable |
Safe Value |
Yes, Programmable |