| Specifications |
| Communication |
| Interface | RS-485 |
| Format | (N, 8, 1) |
| Baud Rate | 1200 ~ 115200 bps |
| Protocol | DCON |
| Dual Watchdog | Yes, Module (1.6 Seconds), Communication (Programmable) |
| LED Indicators/Display |
| System LED Indicator | Yes, 1 LED as Power/Communication Indicator |
| I/O LED Indicators | 8 as AC-SSR Output Indicators |
| Isolation |
| Intra-Module Isolation, Field-toLogic | 3000 VDC |
| EMS Protection |
| ESD (IEC 61000-4-2) | ±4 kV Contact for each Terminal |
| ±8 kV Air for Random Point |
| Power |
| Power Consumption | 0.6 W Max |
| Mechanical |
| Dimensions ( L x W x H) | 115 mm × 30 mm × 102 mm |
| Environment |
| Operating Temperature | -25°C ~ +75°C |
| Storage Temperature | -40°C ~ +85°C |
| Relative Humidity | 10 ~ 95% RH, non-condensing |
| I/O Specification |
| AC Solid State Relay Output |
| Channels | 8 |
| Types | AC SSR (Form A) |
| Form A | Operating Voltage Range | +24 ~ +265 VAC |
| Max. Load Current | 1 A |
| Leakage Current | 1.5 mA |
| Min. Operate Time | 1/2 cycle + 1 ms |
| Min. Release Time | 1/2 cycle + 1 ms |
| Dielectric Strength | 2500 VDC |
| Electrical Endurance | Long Life, No Arcing, No Bounce, No Switching Noise |
| Power-on Value | Yes |
| Safe Value | Yes |