Specifications |
Communication |
Interface | RS-485 |
Format | (N, 8, 1) |
Baud Rate | 1200 ~ 115200 bps |
Protocol | DCON |
Dual Watchdog | Yes, Module (1.6 Seconds), Communication (Programmable) |
LED Indicators/Display |
System LED Indicator | Yes, 1 LED as Power/Communication Indicator |
I/O LED Indicators | 8 as Power Relay Indicators |
Isolation |
Intra-Module Isolation, Field-toLogic | 3000 VDC |
EMS Protection |
ESD (IEC 61000-4-2) | ±4 kV Contact for each Terminal |
±8 kV Air for Random Point |
Power |
Power Consumption | 1.5 W Max |
Mechanical |
Dimensions ( L x W x H) | 115 mm × 30 mm × 102 mm |
Environment |
Operating Temperature | -25°C ~ +75°C |
Storage Temperature | -40°C ~ +85°C |
Relative Humidity | 10 ~ 95% RH, non-condensing |
I/O Specification |
Relay Output |
Channels | 8 (Form A) |
Types | Power Reley |
Form A | Contact Rating | 5 A @ 250 VAC (Resistive Load) |
5 A @ 30 VDC (Resistive Load) |
Min. Contact Load | 10 mA @ 5 VDC |
Contact Material | Gold-plated Silver Cadmium Alloy |
Operate Time | 6 ms (Max.) |
Release Time | 3 ms (Max.) |
Mechanical Endurance | 2 x 107 ops. |
Electrical Endurance | 1 x 105 ops. |
Power-on Value | Yes |
Safe Value | Yes |