| Specifications |
| Communication |
| Interface | RS-485 |
| Format | N, 8, 1 |
| Baud Rate | 1200 ~ 115200 bps |
| Protocol | DCON |
| Dual Watchdog | Yes, Module (1.6 Seconds), Communication (Programmable) |
| LED Indicators/Display |
| System LED Indicator | 1 LED as Power/Communication Indicator |
| I/O LED Indicator | 16 LEDs as High/Low Alarm Signals |
| Isolation |
| Intra-module Isolation, Field-to-Logic | 3750 Vrms |
| EMS Protection |
| ESD (IEC 61000-4-2) | 4 kV Contact for each Terminal |
| 8 kV Air for Random Point |
| Power |
| Power Consumption | 1.0W Max. |
| Dimensions |
| 30mm x 102mm x 115mm(W x L x H) |
| Environment |
| Operating Temperature | -25 to 75°C |
| Storage Temperature | -40 to 75°C |
| Humidity | 10 to 95% RH, non-condensing |
| I/O Specifications |
| Digital Output |
| Channels | 16 |
| Type | Open Collector |
| Sink/Source (NPN/PNP) | Sink |
| Load Voltage | 5 VDC ~ 30 VDC |
| Max. Load Current | 100 mA/ channel |
| Output Voltage | - |
| Output Current | - |
| Overvoltage Protection | - |
| Overload Protection | - |
| Short-circuit and Overcurrent Protection | - |
| Thermal Overload Trip Temperature | - |
| Power-on Value | Yes |
| Safe Value | Yes |
| Watchdog |
| Dual Watchdog | Yes, Module(1.6 sec) and Communication(Programable) |
| Safe Value (When Host Fail or Communication Fail) | Yes |
| Power ON Preset Value | Yes |
| LED Display |
| 1 LED as Power/Communication Indicator |
| 16 LEDs as Digital Output indicators |
| Power |
| Input Voltage Range | 10 ~ 30 VDC |
| Power Consumption | 0.4 W |
| Environment |
| Operating Temperature | -25 to 75°C |
| Storage Temperature | -40 to 75°C |
| Humidity | 5 to 95% RH, non-condensing |
| Dimensions |
| 30mm x 102mm x 115mm(W x L x H) |