Specifications |
Communication |
Interface |
RS-485 |
Format |
(N, 8, 1) |
Baud Rate |
1200 ~ 115200 bps |
Protocol |
DCON |
Dual Watchdog |
Yes, Module (1.6 Seconds), Communication (Programmable) |
LED Indicators/Display |
System LED Indicator |
Yes, 1 LED as Power/Communication Indicator |
I/O LED Indicators |
- |
Isolation |
Intra-Module Isolation, Field-toLogic |
1000 VDC |
EMS Protection |
ESD (IEC 61000-4-2) |
±4 kV Contact for each Terminal |
±8 kV Air for Random Point |
RS Immunity (IEC 61000-4-3) |
- |
Power |
Power Consumption |
1.4 W Max |
Mechanical |
Dimensions ( W x L x H) |
31 mm x 81 mm x 114 mm |
Environment |
Operating Temperature |
-25°C ~ +75°C |
Storage Temperature |
-40°C ~ +85°C |
Relative Humidity |
10 ~ 95% RH, non-condensing |
I/O Specification |
Digital Input |
Channels |
8 |
Current Output Wiring |
Sink |
Range |
0 ~ +20 mA, |
+4 ~ +20 mA |
Resolution |
12-bit |
Accuracy |
+/- 0.1% of FSR |
Zero Drift |
+/- 0.2 µV/°C |
Span Drift |
+/- 25 ppm/°C |
DA Output Respones Time |
10 ms per channel |
Programmable Output Slope |
Voltage |
- |
Current |
0.125 ~ 1024 mA/Second |
Current Output Capacity |
External +24 VDC @ 1050 Ω |
Channel-to-Channel Isolation |
Yes, 1 kV - |
Open Wire Detection |
Yes, +4 ~ +20 mA |
Short Circuit Protection |
Yes |
Power-on Value |
Yes |
Safe Value |
Yes |
External Power Requirements |
Reverse Polarity Protection |
- |
Powered from Terminal Block |
- |
Consumption |
- |