| Specifications |
| Communication |
| Interface | RS-485 |
| Format | (N, 8, 1) |
| Baud Rate | 1200 ~ 115200 bps |
| Protocol | DCON |
| Dual Watchdog | Yes, Module (1.6 Seconds), Communication (Programmable) |
| LED Indicators/Display |
| System LED Indicator | Yes, 1 LED as Power/Communication Indicator |
| I/O LED Indicators | - |
| Isolation |
| Intra-Module Isolation, Field-toLogic | 1000 VDC |
| EMS Protection |
| ESD (IEC 61000-4-2) | ±4 kV Contact for each Terminal |
| ±8 kV Air for Random Point |
| RS Immunity (IEC 61000-4-3) | - |
| Power |
| Power Consumption | 1.4 W Max |
| Mechanical |
| Dimensions ( W x L x H) | 31 mm x 81 mm x 114 mm |
| Environment |
| Operating Temperature | -25°C ~ +75°C |
| Storage Temperature | -40°C ~ +85°C |
| Relative Humidity | 10 ~ 95% RH, non-condensing |
| I/O Specification |
| Digital Input |
| Channels | 8 |
| Current Output Wiring | Sink |
| Range | 0 ~ +20 mA, |
| +4 ~ +20 mA |
| Resolution | 12-bit |
| Accuracy | +/- 0.1% of FSR |
| Zero Drift | +/- 0.2 µV/°C |
| Span Drift | +/- 25 ppm/°C |
| DA Output Respones Time | 10 ms per channel |
| Programmable Output Slope | Voltage | - |
| Current | 0.125 ~ 1024 mA/Second |
| Current Output Capacity | External +24 VDC @ 1050 Ω |
| Channel-to-Channel Isolation | Yes, 1 kV - |
| Open Wire Detection | Yes, +4 ~ +20 mA |
| Short Circuit Protection | Yes |
| Power-on Value | Yes |
| Safe Value | Yes |
| External Power Requirements |
| Reverse Polarity Protection | - |
| Powered from Terminal Block | - |
| Consumption | - |