Broken Line Detection version of I-87018-G I-87018/BL/R has a serial bus (RS-485) communication interface with DCON protocol. It can be plugged into our WinCon, LinCon, I-8000 controllers and I-87K, RF-87K I/O expansion units. I-87018/R is a Thermocouple Input Module with 8 channels. I-87018/R is a serial cartridge based I/O module that offers the ultimate in cost effective flexibility.
Features: - Analog Input Channels : 8 diff.
- Input Type : mV, V, mA (requires optional external 125 O resistor), Thermocouple (J/K/T/E/R/S/B/N/C/L/M/L2)
- Input Impedance : 20 MO
- Sampling Rate : 10Hz (total)
- Accuracy : +/-0.1%
- C.M.R. : 150dB @50/60Hz
- N.M.R. : 100dB @50/60Hz
- Overvoltage Protection : -35 ~ +35V
- Isolation : 3000Vrms
- Power Consumption : 1W