Technical data |
CPU Module |
Watchdog Timer |
Yes, Module (1.6 Seconds), Communication (Programmable) |
Isolation |
Intra-module Isolation |
3000 VDC |
EMS Protection |
EFT (IEC 61000-4-4) |
±4 kV to Power |
ESD (IEC 61000-4-2) |
±4 kV Contact for each Terminal |
Surge (IEC 61000-4-5) |
±0.5 kV for Power Line |
LED Indicators |
Status |
1 x Power and Communication |
Analog Input |
Channels |
6 Differential and 2 Single-ended, or 8 Differential |
Type |
Voltage Current Thermocouple |
Sensor Type |
Thermocouple: J, K, T, E, R, S, B, N, C |
Range |
Voltage: ±15 mV, ±50 mV, ±100 mV, ±500 mV, ±1 V, ±2.5 V Current: ±20 mA, 0 ~ +20 mA, +4 ~ +20 mA (requires an optional external 125 O resistor) |
Resolution |
16-bit |
Accuracy |
±0.1% of FSR |
Sampling Rate |
10 Hz (Total) |
Input Impedance |
> 400 kO |
Common Voltage Protection |
25 VDC |
Overvoltage Protection |
±120 VDC |
Individual Channel Configuration |
- |
COM Ports |
Ports |
1 x RS-485 |
Baud Rate |
1200 to 115200 bps |
Data Format |
(N, 8, 1) (N, 8, 2) (E, 8, 1) (O, 8, 1) |
Protocol |
DCON |
Power |
Reverse Polarity Protection |
Yes |
Input Range |
+10 ~ +30 VDC |
Consumption |
1.0 W |
Mechanical |
Dimensions (mm) |
123 x 72 x 35 (W x L x H) |
Installation |
DIN-Rail |
Environmental |
Operating Temperature |
-25 ~ +75 °C |
Storage Temperature |
-40 ~ +85 °C |
Humidity |
10 ~ 95% RH, Non-condensing |