| Technical Specifications |
| Analog Input |
| Channels | 8 |
| Wiring | Differential |
| Input Range | ±20 mA, 0 ~ 20 mA, 4 ~ 20 mA |
| Resolution | 16-bit |
| Accuracy | Normal Mode 0.1% |
| Sampling Rate | Normal Mode 10 Hz |
| Current | 125 O |
| Common Voltage Protection | ±15 VDC ±200 VDC ±15 VDC |
| Overcurrent Protection | Yes, 50 mA at 110 VDC |
| Open Wire Detection for 4 ~ 20 mA | Yes |
| Communication |
| Interface | RS-485 |
| Format | (N, 8, 1), (N, 8, 2), (E, 8, 1), or (E, 8, 2) |
| Baud Rate | 1200 ~ 115200 bps |
| Protocol | DCON (For I-7017 series) |
| Modbus | RTU, DCON (For M-7017 series) |
| Dual Watchdog | Yes, Module (1.6 Seconds), Communication (Programmable) |
| LED Indicator/Display |
| System LED Indicator | Yes, 1 LED as Power/Communication Indicator |
| Isolation |
Intra-Module Isolation, Field-to-Logic | 3000 VDC |
| EMS Protection |
| ESD (IEC 61000-4-2) | ±4 kV Contact for each Terminal |
| EFT (IEC 61000-4-4) | ±4 kV to Power Line |
| Surge (IEC 61000-4-5) | ±0.5 kV for Power Line |
| Power |
| Reverse Polarity Protection | Yes |
| Input Range | 10 ~ 30 VDC |
| Consumption | 1.3 W |
| Mechanical |
| Dimensions (W x L x H) | 72 mm x 123 mm x 35 mm |
| Installation | DIN-Rail or Wall Mounting |
| Environment |
| Operating Temperature | -25 ~ +75°C |
| Storage Temperature | -40 ~ +85°C |
| Humidity | 10 ~ 95% RH, Non-condensing |