Technical Specifications |
Analog Input |
Channels |
8 |
Wiring |
Differential |
Input Range |
±20 mA, 0 ~ 20 mA, 4 ~ 20 mA |
Resolution |
16-bit |
Accuracy |
Normal Mode 0.1% |
Sampling Rate |
Normal Mode 10 Hz |
Current |
125 O |
Common Voltage Protection |
±15 VDC ±200 VDC ±15 VDC |
Overcurrent Protection |
Yes, 50 mA at 110 VDC |
Open Wire Detection for 4 ~ 20 mA |
Yes |
Communication |
Interface |
RS-485 |
Format |
(N, 8, 1), (N, 8, 2), (E, 8, 1), or (E, 8, 2) |
Baud Rate |
1200 ~ 115200 bps |
Protocol |
DCON (For I-7017 series) |
Modbus |
RTU, DCON (For M-7017 series) |
Dual Watchdog |
Yes, Module (1.6 Seconds), Communication (Programmable) |
LED Indicator/Display |
System LED Indicator |
Yes, 1 LED as Power/Communication Indicator |
Isolation |
Intra-Module Isolation, Field-to-Logic |
3000 VDC |
EMS Protection |
ESD (IEC 61000-4-2) |
±4 kV Contact for each Terminal |
EFT (IEC 61000-4-4) |
±4 kV to Power Line |
Surge (IEC 61000-4-5) |
±0.5 kV for Power Line |
Power |
Reverse Polarity Protection |
Yes |
Input Range |
10 ~ 30 VDC |
Consumption |
1.3 W |
Mechanical |
Dimensions (W x L x H) |
72 mm x 123 mm x 35 mm |
Installation |
DIN-Rail or Wall Mounting |
Environment |
Operating Temperature |
-25 ~ +75°C |
Storage Temperature |
-40 ~ +85°C |
Humidity |
10 ~ 95% RH, Non-condensing |