Technical specifications |
RTD Input Module |
Channels |
1 |
Wiring |
2/3/4-wire |
Sensor Typ |
Pt100, Pt1000, Ni120 |
Resolution |
16-bit |
Accuracy |
±0.05% |
Sampling Rat |
10 Hz |
Individual Channel Configuration |
No |
Overvoltage Protection |
±5 VDC |
Open Wire Detectio |
Yes |
3-wire RTD Lead Resistance Elimination |
Yes |
Resistance Measurement |
3.2 kO Max. |
Communication |
Interfac |
RS-485 |
Bias Resisto |
No (Usually supplied by the RS-485 Master. Alternatively, add a tM-SG4 or SG-785.) |
Format |
(N, 8, 1) (N, 8, 2) (E, 8, 1) (O, 8, 1) |
Baud Rat |
1200 to 115200 bps |
Protocol |
DCON |
Dual Watchdo |
Yes, Module (1.6 Seconds), Communication (Programmable) |
LED Indicator/Display |
System LED Indicator |
Yes, 1 as Power/Communication Indicator |
I/O LED Indicato |
- |
7-Segment LED Displa |
Yes |
Isolation |
Intra-Modul |
Isolation, Field-to-Logic 3000 VDC |
EMS Protection |
ESD (IEC 61000-4-2 |
±2 kV Contact for each Terminal |
EFT (IEC 61000-4-4 |
±4 kV to Power Line |
Surge (IEC 61000-4-5 |
±0.5 kV for Power Line |
Power |
Reverse Polarity Protectio |
Yes |
Input Rang |
+10 ~ +30 VDC |
Consumptio |
1.3 W |
Mechanical |
Dimensions (L x W x H) |
123 mm x 72 mm x 35 mm |
Installation |
DIN-Rail or Wall Mounting |
Environment |
Operating Temperature |
-25 to +75°C |
Storage Temperature |
-40 to +85°C |
Humidity |
10 to 95% RH, Non-condensing |