Technical specifications |
CPU Module |
Watchdog Timer |
Yes, Module (1.6 Seconds), Communication (Programmable) |
Display |
Type |
5-Digit 7 Segment LED Display |
Isolation |
Intra-module Isolation |
3000 VDC |
EMS Protection |
EFT (IEC 61000-4-4) |
±4 kV to Power Line |
ESD (IEC 61000-4-2) |
±2 kV Contact for each Terminal |
Surge (IEC 61000-4-5) |
±0.5 kV for Power Line |
LED Indicators |
Status |
1 x Power and Communication |
Analog Input |
Channels |
1 Differential |
Type |
Voltage Current Thermocouple |
Sensor Type |
Thermocouple: J, K, T, E, R, S, B, N, C Range Voltage: ±15 mV, ±50 mV, ±100 mV, ±500 mV, ±1 V, ±2.5 V Current: ±20 mA (requires optional external 125 O resistor) |
Resolution |
16-bit |
Accuracy |
±0.1% of FSR |
Sampling Rate |
10 Hz (Total) |
Input Impedance |
> 400 kO |
Common Voltage Protection |
±5 VDC |
Overvoltage Protection |
±5 VDC |
Open Wire Detection |
Yes |
Digital Input/Counter |
Channels |
1 |
Type |
Dry Contact |
Sink/Source (NPN/PNP) |
Source |
Dry Contact, ON Voltage Level |
Close to GND |
Dry Contact, OFF Voltage Level |
Open |
Input Impedance |
3 kO |
Overvoltage Protection |
±30 VDC |
Digital Output |
Channels |
2 |
Type |
Open Collector |
Sink/Source (NPN/PNP) |
Sink |
Load Voltage |
+3.5 ~ +30 VDC |
Max. Load Current |
30 mA/Channel |
Power on Value |
Yes |
Safe Value |
Yes |
COM Ports |
Ports |
1 x RS-485 |
Baud Rate |
1200 to 115200 bps |
Data Format |
N, 8, 1 |
Protocol |
DCON |
Power |
Reverse Polarity Protection |
Yes |
Input Range |
+10 ~ +30 VDC |
Consumptio |
1.5 W |
Mechanical |
Dimensions (mm) |
123 x 72 x 35 (W x L x H) |
Installation |
DIN-Rail |
Environmental |
Operating Temperature |
-25 ~ +75 °C |
Storage Temperature |
-40 ~ +85 °C |
Humidity |
10 ~ 95% RH, Non-condensing |