| Specifications |
| CAN Interface |
| Connector | Screwed terminal block (CAN_GND, CAN_L, CAN_H) |
| Baud Rate (bps) | 10 k ~ 1 M |
| Transmission Distance (m) | Depend on baud rate |
| Terminator Resistor | Switch for 120? terminator resistor |
| Isolation | 2500 Vrms |
| Specification | ISO-11898-2, CAN 2.0A and CAN 2.0B |
| Fiber Interface |
| Connector | ST (Multi-mode) |
| Wave Length | 850 nm |
| Fiber Cable | 50 / 125 µm , 62.5 / 125 µm, 100 / 140 µm (62.5 / 125µm is recommended) |
| Propagation Delay | 125ns max (125ns delay shortens bus line length by ~ 25 m) |
| Transmission Distance (m) | 2 km max (in 62.5 / 125 µm fiber cable) |
| LED |
| Round LED | PWR LED, CAN_Tx LED, CAN_Rx LED, CAN_Err LED, FB_Err LED |
| Power |
| Power supply | Unregulated +10 ~ +30 VDC |
| Protection | Power reverse polarity protection, Over-voltage brown-out protection |
| Power Consumption | 3 W |
| Mechanism |
| Installation | DIN-Rail |
| Dimensions | 32.3mm x 77.5mm x 99.0mm (W x L x H) |
| Environment |
| Operating Temp. | -25 ~ 75° C |
| Storage Temp. | -40 ~ 80° C |
| Humidity | 5 ~ 90% RH, non-condensing |