Technical specifications |
Modbus RTU Slave FEATURES |
Operation Mode | Modbus RTU Slave |
Function Codes Supported | 1,2,3,4,5,6,15 & 16 |
Swapping | Byte and Word Swapping |
Maximum Modbus RTU Master Connections | 1 |
Contiguous Data Areas | 200 Total - 100 reads & 100 writes |
Data Area Limits | 512 Contiguous Coils or 512 Contiguous Registers |
BACnet/IP Client FEATURES |
Operation Mode | BACnet/IP Client |
Supported Object Types | Device, BI/BO/BV, AI/AO/AV, MI/MO/MV, Character String Value |
Supported Service Codes | Read Property-A, Read Property Multiple-A, Write Property-A, Write Property Multiple-A, Device |
Dynamic | Binding-A |
Maximum Connections | 32 |
Number Read/Write Scan Lines per Device | 200 Total - 100 reads & 100 writes |
Scan Line | Support Up to 128 Objects |
ELECTRICAL / ENVIRONMENTAL |
DC Input Voltage | 12-24 VDC |
Maximum Baud Rate | 15K baud |
Operating Temperature | -40 C to 85 C |
Certification | RoHS-Compliant, UL, CUL, CE Approvals |
ENCLOSURE / HARDWARE |
Size | 3.88? x 2.57? x 1.06? |
Weight | 5.5 oz |
Enclosure Type | Anodized Aluminum |
Mounting | Din rail or panel mount |
LEDs Power | LED & 2 general purpose LEDs on side |