| Technical Data |
| GENERAL |
| Standard | EN61010-1 EN61010-2-201 EN61131-2 |
| Dimensions (W × H × D) | 72x90x62mm |
| Weight | 270g |
| Mounting | Top hat rail EN50022, 35mm |
| ENVIRONMENTAL CONDITIONS |
| Operating ambient temperature | 0°C – 55°C |
| Relative humidity – non-condensing | 80 % for temp. up to 31 °C, decreasing linearly to 50 % relative humidity at 55 °C |
| Pollution Degree | PD2 |
| Altitude | up to 2000m AMSL |
| Vibration (5 = f = 9 Hz) | 1,75 mm amplitude sinus 3,5 mm amplitude random |
| Vibration (9 = f = 150 Hz) | 0,5 g acceleration sinus 1,0 g acceleration random |
| Transport and Storage | -20°C – +70°C 10 to 90% no condensation Altitude 3000m AMSL |
| Shock response | 15g, 11ms half sinus all 3 axes |
| I/O |
| Supply voltage | 12V or 24V |
| USB (Power for programming only) | USB-B, 2.0 |
| Ethernet | RJ45, 10/100Mbps |
| RS485 (no termination inside) | 250kb |
| Inputs, no galvanic insulation | 12 |
| Common analog/digital | 10 |
| Fixed digital, ext. Interrupt usable | 2 |
| Digital Outputs, no galvanic insulation | 12 |
| Relay Outputs, galvanic insulation | 5 |
PIN Header, no galvanic insulation Logic level I/Os | 42, partially parallel to terminal I/Os |
| Analog 0-5V Inputs | 14 |
| Communication | SPI, 2xUART, I2C, Reset |
| Internal Power | +3,3V, +5V, ARef, GND |
| TERMINAL CAPACITIES |
| Relay Output, Power Input | 2,5mm² (24-12AWG) |
| Strip length | 6-7mm |
| Max. tightening torque | 0,5Nm |
| Digital, Analog Input Output | 1,5mm² (30-16AWG) |
| Strip length | 5-6mm |
| Max. tightening torque | 0,2Nm |
| Pin header connector | 2x 26 Pin, Dual row, 2.54 pitch |
| PROTECTION |
| ESD HBM Class | 0 Contact discharge: ±4kV Air discharge: ±8kV |
| Supply input over current protection | Internal Fuse 20A |
| Relay Output | External Fuse required |
| Digital Output | Overload, short circuit, ESD |
| Signal Input | Overvoltage, ESD |
| Pin header connector | ESD |