Technical data |
General |
Standard | EN61010-1 EN61010-2-201 EN61131-2 |
Dimensions (W × H × D) | 107x90x62mm |
Weight | 350g |
Mounting | Top hat rail EN50022, 35mm |
Environmental conditions, Indoor use only |
Operating ambient temperature | 0°C – 55°C |
Relative humidity – non-condensing | 80 % for temp. up to 31 °C, decreasing linearly to 50 % relative humidity at 55 °C |
Pollution Degree | PD2 |
Altitude | up to 2000m AMSL |
Vibration (5 = f = 9 Hz) Vibration (9 = f = 150 Hz) | 1,75 mm amplitude sinus 3,5 mm amplitude random 0,5 g acceleration sinus 1,0 g acceleration random |
Transport and Storage | -20°C – +70°C 10 to 90% no condensation Altitude 3000m AMSL |
Shock response | 15g, 11ms half sinus all 3 axes |
I/O |
Supply voltage | 12V or 24V |
USB (Power for programming only) | USB-B, 2.0 |
Ethernet | RJ45, 10/100Mbps |
RS485 (no termination inside) | 250kb |
Inputs, no galvanic insulation Common analog/digital Fixed digital, ext. Interrupt usable | 21 16 5 |
Digital Outputs, no galvanic insulation Relay output | 24 16 |
PIN Header, no Galvanic insulation Logic level Input Logic level Output Communication Internal Power | 21 parallel to terminal Inputs 24 parallel to terminal Outputs SPI, 2xUART, I2C, Reset +3,3V, +5V, ARef, GND |
Terminal capacities |
Relay Output, Power Input Strip length Max. tightening torque | 2,5mm² (24-12AWG) 6-7mm 0,5Nm |
Digital, Analog Input Output Strip length Max. tightening torque | 1,5mm² (30-16AWG) 5-6mm 0,2Nm |
Pin header connector | 2x 26 Pin, Dual row, 2.54 pitch |
Protection |
ESD HBM Class 0 | Contact discharge: ±4kV Air discharge: ±8kV |
Supply input over current protection | Internal Fuse 30A (fast) |
Relay Output | External Fuse required |
Digital Output | Overload, short circuit, ESD |
Signal Input | Overvoltage, ESD |
Pin header connector Current +5V, +3,3V | ESD total 200mA, resettable fuse |