| Technical data |
| General |
| Standard | EN61010-1 EN61010-2-201 EN61131-2 |
| Dimensions (W × H × D) | 72x90x62mm |
| Weight | 270g |
| Mounting | Top hat rail EN50022, 35mm |
| ENVIRONMENTAL CONDITIONS |
| Operating ambient temperature | 0°C – 55°C |
| Relative humidity – non-condensing | 80 % for temp. up to 31 °C, decreasing linearly to 50 % relative humidity at 55 °C |
| Pollution Degree | PD2 |
| Altitude | up to 2000m AMSL |
| Vibration (5 = f = 9 Hz) | 1,75 mm amplitude sinus 3,5 mm amplitude random |
| Vibration (9 = f = 150 Hz) | 0,5 g acceleration sinus 1,0 g acceleration random |
| Transport and Storage | -20°C – +70°C 10 to 90% no condensation Altitude 3000m AMSL |
| Shock response | 15g, 11ms half sinus all 3 axes |
| I/O |
| Supply voltage | 12V or 24V |
| USB (Power for programming only) | USB-B, 2.0 |
| Ethernet | RJ45, 10/100Mbps |
Analog inputs | 2x 0-10 V | Analog outputs | 2x 0-10 V or 0-20 mA | | Inputs, no galvanic insulation | 18 |
| Common analog/digital | 12 |
| Digital | 4 |
| Fixed digital, ext. Interrupt usable | 2 |
| Digital Outputs, no galvanic insulation | 8 |
| Relay Outputs, galvanic insulation | 5 |
| TERMINAL CAPACITIES |
Relay Output, Power Input Strip length Max. tightening torque | 2,5mm² (24-12AWG) 6-7mm 0,5Nm |
Digital, Analog Input Output Strip length Max. tightening torque | 1,5mm² (30-16AWG) 5-6mm 0,2Nm |
| PROTECTION |
| ESD HBM Class 0 | Contact discharge: ±4kV Air discharge: ±8kV |
| Supply input over current protection | Internal Fuse 20A |
| Relay Output | External Fuse required |
| Digital Output | Overload, short circuit, ESD |
| Signal Input | Overvoltage, ESD |