Technical specifications |
GENERAL |
Standard | EN61010-1 EN61010-2-201 EN61131-2 |
Dimensions (W × H × D) | 72x90x62mm |
Weight | 250g |
Mounting | Top hat rail EN50022, 35mm |
ENVIRONMENTAL CONDITIONS |
Operating ambient temperature | 0°C – 55°C |
Relative humidity – non-condensing | 80 % for temp. up to 31 °C, decreasing linearly to 50 % relative humidity at 55 °C |
Pollution Degree | PD2 |
Altitude | up to 2000m AMSL |
Vibration (5 = f = 9 Hz) | 1,75 mm amplitude sinus 3,5 mm amplitude random |
Vibration (9 = f = 150 Hz) | 0,5 g acceleration sinus 1,0 g acceleration random |
Transport and Storage | -20°C – +70°C 10 to 90% no condensation Altitude 3000m AMSL |
Shock response | 15g, 11ms half sinus all 3 axes |
I/O |
Supply voltage | 12V or 24V |
USB (Power for programming only) | USB-B, 2.0 |
Ethernet | RJ45, 10/100Mbps |
RS485 (no termination inside) | 250kb |
Inputs, no galvanic insulation | 12 |
Common analog/digital | 10 |
Fixed digital, ext. Interrupt usable | 2 |
Digital Outputs, no galvanic insulation | 12 |
Relay Outputs, galvanic insulation | 10 |
TERMINAL CAPACITIES |
Relay Output, Power Input Strip length Max. tightening torque | 2,5mm² (24-12AWG) 6-7mm 0,5Nm |
Digital, Analog Input Output Strip length Max. tightening torque | 1,5mm² (30-16AWG) 5-6mm 0,2Nm |
PROTECTION |
ESD HBM Class 0 | Contact discharge: ±4kV Air discharge: ±8kV |
Supply input over current protection | Internal Fuse 20A |
Relay Output | External Fuse required |
Digital Output | Overload, short circuit, ESD |
Signal Input | Overvoltage, ESD |