| Technical Specifications |
| GENERAL |
| Standard | EN61010-1 EN61010-2-201 EN61131-2 |
| Dimensions (W × H × D) | 36x90x60mm |
| Weight | 145g |
| Mounting Top hat rail | EN50022, 35mm |
| ENVIRONMENTAL CONDITIONS |
| Operating ambient temperature | 0°C – 55°C |
| Relative humidity – non-condensing | 80 % for temp. up to 31 °C, decreasing linearly to 50 % relative humidity at 55 °C |
| Pollution Degree | PD2 |
| Altitude | up to 2000m AMSL |
| Vibration (5 = f = 9 Hz) | 1,75 mm amplitude sinus 3,5 mm amplitude random |
| Vibration (9 = f = 150 Hz) | 0,5 g acceleration sinus 1,0 g acceleration random |
| Transport and Storage | -20°C – +70°C 10 to 90% no condensation |
| Altitude | 3000m AMSL |
| Shock response | 15g, 11ms half sinus all 3 axes |
| I/O |
| Supply voltage | 12V or 24V |
| USB (Power for programming only) | USB-B, 2.0 |
Inputs, no galvanic insulation Common analog/digital Fixed digital Fixed analog | 8 4 2 2 |
| Digital Outputs, no galvanic insulation | 8 |
| Relay Outputs (parallel to Digital, galvanic ins.) | 6 |
| TERMINAL CAPACITIES |
Relay Output, Power Input Strip length Max. tightening torque | 2,5mm² (24-12AWG) 6-7mm 0,5Nm |
Digital, Analog Input Output Strip length Max. tightening torque | 1,5mm² (30-16AWG) 5-6mm 0,2Nm |
| PROTECTION |
| ESD HBM Class 0 | Contact discharge: ±4kV Air discharge: ±8kV |
| Supply input over current protection | Internal Fuse 8A |
| Relay Output | External Fuse required |
| Digital Output | Overload, short circuit, ESD |
| Signal Input | Overvoltage, ESD |